1. Supports single-phase 115V/230V dual voltage modes, adapting to different regional power standards and allowing for installation and use without additional modifications.
2. Equipped with industrial-grade, high-strength ball bearings, it significantly improves mechanical stability and durability, reduces vibration and wear, and extends service life.
3. The forward-curved design and galvanized steel material optimize aerodynamic performance, achieving efficient airflow while maintaining low noise, meeting high-flow ventilation needs.
4. Compatible with 50Hz/60Hz broadband frequencies, it meets the operational needs of diverse global scenarios, ensuring exceptional adaptability.
Main Datas:
| Condition No. | Static Pressure of Air Chamber (Pa) | Air Flow (m³/h) | Total Pressure of Air Chamber (Pa) | Current (A) | Speed (r/min) | Power (W) |
| 1 | 347.45 | 103.55 | 363.4 | 1.45 | 1456 | 250 |
| 2 | 308.54 | 248.7 | 324.49 | 1.46 | 1452 | 262 |
| 3 | 285.83 | 373.72 | 301.79 | 1.47 | 1447 | 267 |
| 4 | 253.06 | 642.44 | 269.01 | 1.5 | 1430 | 284 |
| 5 | 220.1 | 1098.88 | 236.07 | 1.58 | 1396 | 316 |
| 6 | 183.11 | 1410.61 | 199.09 | 1.69 | 1358 | 350 |
| 7 | 121.4 | 1774.47 | 137.4 | 1.91 | 1295 | 404 |
| 8 | 85.51 | 1907.15 | 101.51 | 2.03 | 1254 | 435 |
| 9 | 52.09 | 2000.56 | 68.09 | 2.11 | 1220 | 455 |
| 10 | 14.19 | 2094.35 | 30.19 | 2.24 | 1165 | 482 |
Product size:
Curve:
Products provided by famous enterprises are deeply trusted by users.
What Causes Blower Impeller Noise and Vibration? The abnormal noise or vibration in a blower impeller is most commonly caused by physical imbalance (over 70% of field service cases), followed by bearing failure, loose mounting, or foreign object debris. If the impeller is not perfectly balanced, even a slight weight d...